AI-assisted anomaly detection can be evaluated as a way to flag unusual patterns in historian data for human review. An anomaly is a departure from an expected pattern; it is not, by itself, a diagnosis, a confirmed incident, or an instruction to change equipment operation.
This guide describes evaluation considerations. Any Mangan continuity integration with historian data or AI analytics requires confirmation of the proposed scope, supported interfaces, and responsibilities. It should not be read as a specification of a standard AI feature.
Start with a defined operational question
Choose a use case narrow enough to test, such as identifying an unusual relationship between recorded flow and transaction status. Agree which team reviews the output, what supporting records it needs, and how the review fits existing procedures. Avoid starting with a broad promise to predict every incident.
An analytical notification should not replace site alarms, interlocks, protective systems, or approved operating procedures. Any proposed use that affects equipment control needs its own engineering and site approval process.
Check historian data before evaluating a model
- Tag meaning: record the measurement, engineering unit, source, and responsible owner.
- Time alignment: check timestamps, sampling intervals, and clock differences across systems.
- Data quality: identify missing values, stale readings, maintenance periods, and instrument changes.
- Operating context: distinguish startup, shutdown, maintenance, and normal production or transfer states.
- Transaction context: confirm whether movement status and quantity records can be matched to the historian period.
A gap in recorded data may look unusual without representing an equipment problem. Preserve quality flags and operating context so reviewers can distinguish a process change from a data issue.
Compare the model with an understandable baseline
Evaluate whether a simple threshold, rate-of-change rule, or existing review process already addresses the selected use case. Test a proposed model on a separate period of history and examine the results with people who understand the site’s operations.
Track false alerts, missed events where suitable reviewed examples exist, notification delay, and the work required to investigate. A high count of detected anomalies is not evidence of improved reliability. Review whether the output provides useful information early enough for the intended decision.
Design the review workflow
- Show the relevant tags, time window, quality flags, and available transaction context.
- Route the notification to an accountable reviewer using an agreed escalation process.
- Record whether the finding was a data issue, expected operating change, or matter requiring follow-up.
- Link follow-up to the site’s existing maintenance or operational process.
- Review recurring false alerts and document changes to the analytical configuration.
For example, an unusual flow pattern during a planned instrument service may be expected. A reviewer needs the service record and data-quality indicators before drawing a conclusion. The model output should support that review rather than present a cause as established fact.
Agree deployment boundaries
Before a pilot, document data access, security review, model ownership, change control, retention, support, and behavior when the data feed is unavailable. Set an acceptance threshold and identify who can pause the pilot if notifications become misleading or burdensome.
The NIST AI Risk Management Framework offers voluntary guidance for managing AI risks. It can help structure evaluation and governance, but does not certify a model’s performance or safety.
Connect analytics to usable operational records
Review Advanced Reporting and the terminal management system when defining the records and reporting needed for a proposed integration. Confirm historian connectivity and any analytical functionality separately.
Frequently asked questions
Does an anomaly mean equipment is about to fail?
No. It indicates an unusual pattern relative to the method’s expectations. Instrument issues, missing data, and legitimate operating changes can also produce unusual patterns. A qualified reviewer must assess the evidence.
Can anomaly detection replace existing alarms?
This evaluation approach does not establish that suitability. Keep existing alarm, protection, and operating responsibilities intact unless a separate approved engineering process determines otherwise.